DSP-33125K12MHK-(J)
DASS Tech’s 125kW 12-MPPT String Inverter —
Proven Design and Field-Verified Reliability
| Input Specifications |
| Start-up Voltage (Vdc) | 300V | |
| Operating Voltage Range | 140V ~ 1000V | |
| MPPT Voltage Range (Full Load) | 245V ~ 800V (32A FUSE) | |
| Rated Voltage (Vdc) | 650V | |
| Maximum Open Circuit Voltage (Vdc) | 1000V | |
| Maximum Input Current (A) / per MPPT | 511.2A / 42.6A (1) | |
| Input Terminal | 24EA | |
| MPPT Control Terminal | 12EA | |
| Control Method | Maximum Power Point Tracking (MPPT) Control, PWM Method | |
| Input Blocking Capacity | 400A (2) | |
| Output Specifications |
| Rated Output Capacity (kW) | 125kW | |
| Rated Voltage (Vac) | Grid Voltage (AC380V +10%, -12%) | |
| Frequency Fluctuation Rate (Hz) | Grid Frequency (60Hz +0.5Hz, -0.7Hz) | |
| Power Factor (%) | 0.98 or higher (+0.9 ~ -0.9) | |
| Anti-Islanding Method | Within 0.5 seconds | |
| Overload (%) | 110%, 10 Minutes | |
| Efficiency (%) | 98% or Higher | |
| Total Harmonic Distortion | Total 5% or Less (3% or Less for Each Order) | |
| Reactive Power Control | Korea Electric Power Corporation Output Control Function | |
| Output Blocking Capacity | 270A | |
| Structure |
| Cooling Method | Forced Air Cooling Type (FAN) | |
| Ingress Protection rating (IP grade) | IP66 (Outdoor Type) | |
| External Dimensions (WxHxD, mm) | 978.6 X 808.4 X 335.6 | |
| Total Weight (kg) | 100kg | |
| External Interface | RS485 | |
| Service Environment | Ambient Temperature : -20 ~ 50°C, Storage Temperature : -20 ~ 65°C, Humidity : Relative Humidity 90% R.H. or Less (No Dew Formation) | |
| Protection Function | Input Overvoltage, Output Short Circuit, Overload, Inverter Overheat Protection, DC Output Leakage Prevention, Isolated Operation Prevention (IEEE1547), Grid Overvoltage / Low Voltage Protection, Grid Overfrequency / Low Frequency Protection | |
| Other Function | PV Insulation Resistance Monitoring, SPD Fault Monitoring, Relay Fault Monitoring, Insulation Condition Monitoring, Residual Current Monitoring (RCMU) | |
| Junction Box FUSE Rating | 1000V / 32A / 20kA | |
| Commercial Power | Not Required | |
| Certification | KS C 8565 | |
| Notes | (1) Input Current per MPPT Control Channel (Integrated Junction Box) (2) DC SWITCH (based on rating 1000V) (3) RELAY Blocking Capacity (based on 800V) |
|
Related documents